Free Service Entrance Sizing Practice Questions
Master Electrician License Exam · Services & Feeders
This module covers Service Entrance Sizing as part of the Services & Feeders section, testing your understanding of core concepts and their practical application.
| Exam | Master Electrician License Exam |
| Pass Rate | 45% |
| Duration | 300 minutes |
| Module | Service Entrance Sizing |
Why Service Entrance Sizing matters
Service Entrance Sizing is heavily tested because undersized conductors and services cause overheating, fires, and equipment failure.
Sample Practice Questions (5)
1. A commercial building has a calculated demand load of 800 amperes at 480Y/277V, 3-phase. The service entrance conductors must be sized per NEC 230.42. If using parallel sets of conductors, what is the minimum number of 500 kcmil THWN-2 copper conductors per phase required? (500 kcmil THWN-2 Cu = 380A at 75°C)
- 3 conductors per phase (3 × 380 = 1,140A capacity)
- 2 conductors per phase (2 × 380 = 760A capacity)
- 4 conductors per phase
- 1 conductor per phase
2. A large industrial facility requires two services per NEC 230.2(A) due to capacity requirements exceeding 2,000 amperes at 480V. Per 230.2(D), what additional requirement applies?
- A permanent plaque or directory shall be installed at each service disconnect location denoting all other services supplying the building and the area served by each
- Each service must have its own utility meter only
- The services must be on opposite sides of the building
- A transfer switch must be installed between the two services
3. NEC 230.44 requires that when service entrance conductors are run in parallel, each set must have which characteristic?
- Each parallel conductor set must be the same length, same material, same circular mil area, same insulation type, and terminated in the same manner
- Parallel conductors may be different sizes if the total ampacity meets the load
- Each set must be in the same raceway
- Parallel conductors are only permitted for feeders, not service entrance conductors
Want more practice like this?
Start practicing free →4. Service entrance conductors supplying a 200-ampere, 120/240V, single-phase dwelling must be sized to carry at least what amperage?
- 200 amperes — service entrance conductors must have an ampacity not less than the rating of the service disconnect
- 250 amperes (125% of 200A)
- 175 amperes (allowing for diversity)
- 150 amperes (with demand factor applied)
5. Under which NEC exception is a second service permitted for a single building?
- When the building has a fire pump requiring a separate service per 230.2(A)(1)
- When the building exceeds 5,000 square feet
- When the building is three or more stories tall
- When requested by the building owner for convenience