TL;DR
Learn the specific NEC requirements for swimming pools, spas, and fountains including bonding and clearance rules. These specialty installations have strict safety requirements.
Free Swimming Pools & Fountains (Art. 680) Practice Questions
Master Electrician License Exam · Special Equipment
This module covers Swimming Pools & Fountains (Art. 680) as part of the Special Equipment section, testing your understanding of core concepts and their practical application.
| Exam | Master Electrician License Exam |
| Pass Rate | 45% |
| Duration | 300 minutes |
| Module | Swimming Pools & Fountains (Art. 680) |
Why Swimming Pools & Fountains (Art. 680) matters
Swimming Pools & Fountains (Art. 680) is a commonly tested topic on the Master Electrician License Exam because it covers fundamental knowledge required for competent professional practice.
Sample Practice Questions (5)
1. Per NEC 680.23(F)(2), a GFCI-protected branch circuit supplying an underwater luminaire operating at more than 15 volts must have the GFCI device installed where?
- Not less than 5 feet from the inside wall of the pool, unless it is part of a listed assembly that is behind a solid fence, wall, or other enclosure
- Inside the pool equipment room only
- At the main service panel
- Within 3 feet of the pool edge
2. Per NEC 680.26(C), which of the following must be included in the equipotential bonding for a permanently installed pool?
- All metallic parts of the pool structure, metal fittings within or attached to the pool, forming shells, deck reinforcing steel, and metal parts of electrical equipment associated with the pool water circulating system
- Only the pool pump and heater
- Only metal ladders and handrails
- Only the pool light fixture junction box
3. Per NEC 680.23(A)(3), a forming shell for an underwater luminaire installed in the wall of a pool must be equipped with what provision?
- A means for terminating an 8 AWG copper equipment grounding conductor and must have the number of conduit entries required for the luminaire
- Only a GFCI breaker internal to the shell
- A waterproof seal tested to 50 PSI
- A minimum 4-inch square junction box
Want more practice like this?
Start practicing free →4. Per NEC 680.22(B)(6), luminaires, lighting outlets, and ceiling-suspended paddle fans must not be installed over a pool or within what horizontal distance from the inside wall of the pool unless they are at least 12 feet above the maximum water level?
- 5 feet
- 10 feet
- 3 feet
- 20 feet
5. Per NEC 680.26(B)(1), the equipotential bonding conductor used for the pool bonding grid must be a minimum of what size?
- 8 AWG solid copper
- 12 AWG stranded copper
- 6 AWG copper
- 10 AWG solid copper
Ready to practice for the Master Electrician License Exam?
Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.
Start free practice →