TL;DR
Study ratio and proportion concepts used in scaling, voltage dividers, and material calculations. Proportional reasoning appears throughout electrical work.
Free A/C & Refrigeration (Art. 440) Practice Questions
Master Electrician License Exam · Special Equipment
This module covers A/C & Refrigeration (Art. 440) as part of the Special Equipment section, testing your understanding of core concepts and their practical application.
| Exam | Master Electrician License Exam |
| Pass Rate | 45% |
| Duration | 300 minutes |
| Module | A/C & Refrigeration (Art. 440) |
Why A/C & Refrigeration (Art. 440) matters
A/C & Refrigeration (Art. 440) is a commonly tested topic on the Master Electrician License Exam because it covers fundamental knowledge required for competent professional practice.
Sample Practice Questions (5)
1. Two A/C compressors are supplied by a single feeder. Compressor 1 has an RLA of 30A and Compressor 2 has an RLA of 45A. Both are single-phase. Per NEC 440.33, what is the minimum feeder conductor ampacity?
- 86.25 amperes
- 75 amperes
- 93.75 amperes
- 56.25 amperes
2. A rooftop A/C package unit has a compressor RLA of 65A and a BCSC of 80A. Per NEC 440.22(A), what is the maximum circuit breaker size permitted for branch circuit protection?
- 150 amperes
- 113.75 amperes
- 100 amperes
- 175 amperes
3. A 3-phase A/C unit has a compressor RLA of 40A and a condenser fan motor FLA of 5A. The nameplate BCSC is 50A. Per NEC 440.33, what is the minimum conductor ampacity for the circuit supplying this unit?
- 55 amperes
- 50 amperes
- 56.25 amperes
- 45 amperes
Want more practice like this?
Start practicing free →4. Per NEC 440.22(A), the rating of the branch circuit short-circuit and ground-fault protective device for a motor-compressor shall not exceed what value?
- 175% of the rated-load current or branch circuit selection current, whichever is greater
- 125% of the rated-load current
- 250% of the rated-load current
- 200% of the branch circuit selection current
5. A single-phase A/C compressor has a rated-load current (RLA) of 28 amperes and a branch circuit selection current (BCSC) of 35 amperes on the nameplate. Per NEC 440.32, what is the minimum conductor ampacity?
- 43.75 amperes
- 35 amperes
- 28 amperes
- 56 amperes
Ready to practice for the Master Electrician License Exam?
Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.
Start free practice →