TL;DR
Study renewable energy system installation requirements including photovoltaic arrays. Solar installations are a growing field with specific NEC requirements.
Free Solar PV Systems (Art. 690) Practice Questions
Master Electrician License Exam · Advanced NEC
This module covers Solar PV Systems (Art. 690) as part of the Advanced NEC section, testing your understanding of core concepts and their practical application.
| Exam | Master Electrician License Exam |
| Pass Rate | 45% |
| Duration | 300 minutes |
| Module | Solar PV Systems (Art. 690) |
Why Solar PV Systems (Art. 690) matters
Solar PV Systems (Art. 690) is a commonly tested topic on the Master Electrician License Exam because it covers fundamental knowledge required for competent professional practice.
Sample Practice Questions (5)
1. A rooftop PV array has 12 modules in series per string, each rated at 40.5 Voc (open-circuit voltage) at STC. The lowest expected ambient temperature is -15°C, giving a temperature correction factor of 1.12. What is the maximum system voltage?
- 544.3 V
- 486.0 V
- 40.5 V
- 607.2 V
2. A PV inverter output is connected to a 200A panelboard busbar using the supply-side connection method per NEC 705.12(A). The maximum size of the PV overcurrent device on the busbar is:
- Not limited by the 120% rule; it connects on the supply side of the main overcurrent device
- 40 amps (200 × 0.20)
- 200 amps
- 160 amps (200 × 0.80)
3. Per NEC 690.9(B), the maximum rating of an overcurrent device for a PV source circuit is:
- The value marked on the PV module (series fuse rating) or per manufacturer's instructions
- 125% of Isc multiplied by 125% (156% of Isc)
- 200% of the module short-circuit current in all cases
- The same as the inverter input current rating
Want more practice like this?
Start practicing free →4. A PV system uses the load-side connection method per NEC 705.12(B)(2)(3)(b) on a 200A busbar panel with a 200A main breaker. The maximum PV backfed breaker size using the 120% rule is:
- 40 amps
- 80 amps
- 200 amps
- 60 amps
5. Per NEC 690.12, the rapid shutdown system for a building-mounted PV system must reduce conductors within the array boundary to no more than what voltage within 30 seconds of rapid shutdown initiation?
- 80 volts
- 30 volts
- 120 volts
- 0 volts
Ready to practice for the Master Electrician License Exam?
Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.
Start free practice →