TL;DR
Master conductor sizing, ampacity calculations, and derating factors per NEC tables. Wire sizing is fundamental to electrical safety and one of the most tested exam topics.
Free Conductor Ampacity (Table 310.16) Practice Questions
Journeyman Electrician License Exam · Wiring Methods & Materials
This module covers Conductor Ampacity (Table 310.16) as part of the Wiring Methods & Materials section, testing your understanding of core concepts and their practical application.
| Exam | Journeyman Electrician License Exam |
| Pass Rate | 55% |
| Duration | 240 minutes |
| Module | Conductor Ampacity (Table 310.16) |
Why Conductor Ampacity (Table 310.16) matters
Conductor Ampacity (Table 310.16) is heavily tested because undersized conductors and services cause overheating, fires, and equipment failure.
Sample Practice Questions (5)
1. Eight 10 AWG THHN copper conductors are installed in a single conduit in an ambient temperature of 40°C. Per Table 310.16 and the applicable correction/adjustment factors, what is the adjusted ampacity of each conductor? (90°C base ampacity of 10 AWG = 40A; 40°C correction factor for 90°C = 0.91; adjustment for 8 CCC = 70%)
- 25.48 amperes
- 28 amperes
- 32 amperes
- 36.4 amperes
2. A conduit contains three 3-wire circuits (9 current-carrying conductors) of 8 AWG THHN copper. The ambient temperature is 30°C. What is the adjusted ampacity per conductor? (90°C base for 8 AWG = 55A; adjustment for 7-9 CCC = 70%)
- 38.5 amperes
- 55 amperes
- 44 amperes
- 27.5 amperes
3. Six 6 AWG THHN copper conductors (90°C, 75A each) are installed in a conduit in an ambient temperature of 45°C. What is the adjusted ampacity? (45°C correction for 90°C = 0.87; 6 CCC adjustment = 80%)
- 52.2 amperes
- 60 amperes
- 65.25 amperes
- 45.68 amperes
Want more practice like this?
Start practicing free →4. Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 14 AWG copper conductors?
- 15 amperes
- 20 amperes
- 25 amperes
- 30 amperes
5. A 4 AWG THWN-2 copper conductor has a 90°C ampacity of 95A per Table 310.16. However, the termination at the equipment is rated for 75°C only. What ampacity must be used for this conductor per NEC 110.14(C)?
- 85 amperes (75°C column value)
- 95 amperes (90°C column value)
- 70 amperes (60°C column value)
- 100 amperes
Ready to practice for the Journeyman Electrician License Exam?