Skip to main content

TL;DR

Master conductor sizing, ampacity calculations, and derating factors per NEC tables. Wire sizing is fundamental to electrical safety and one of the most tested exam topics.

By Valenke Exam Prep Team·Last updated 2026-06-03

Free Conductor Protection Practice Questions

Journeyman Electrician License Exam · Overcurrent Protection

This module covers Conductor Protection as part of the Overcurrent Protection section, testing your understanding of core concepts and their practical application.

ExamJourneyman Electrician License Exam
Pass Rate55%
Duration240 minutes
ModuleConductor Protection

Why Conductor Protection matters

Conductor Protection is one of the most tested NEC topics because improper grounding and protection cause electrical fires and fatalities.

Sample Practice Questions (5)

1. Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 12 AWG copper conductors?

  • 15A
  • 20A
  • 25A
  • 30A

2. A 2 AWG THHN copper conductor (90°C ampacity = 130A) is installed in a conduit with 5 other current-carrying conductors (6 total). The adjusted ampacity is used with 75°C terminations. What is the maximum OCPD rating using the next standard size up rule?

  • 100A
  • 110A
  • 90A
  • 125A

3. Per NEC 110.14(C)(1), equipment with terminations rated for 60°C requires conductors to be selected based on which ampacity column of Table 310.16?

  • The 60°C column, even if the conductor insulation is rated higher
  • The 90°C column to maximize ampacity
  • The 75°C column as a compromise
  • Any column, since the conductor insulation rating determines ampacity

Want more practice like this?

Start practicing free →

4. A 6 AWG copper THWN conductor is installed with 75°C-rated terminals. Per NEC Table 310.16 (75°C column), the ampacity is 65 amperes. What is the maximum standard OCPD size permitted to protect this conductor per 240.4(B)?

  • 70 amperes
  • 60 amperes
  • 65 amperes
  • 80 amperes

5. Three 3 AWG THHN copper conductors are installed in a conduit in an ambient temperature of 40°C. Per Table 310.16 (90°C column), the base ampacity is 115A. The temperature correction factor for 40°C in the 90°C column is 0.91. What is the adjusted ampacity, and what OCPD size should be selected assuming 75°C terminals?

  • Adjusted ampacity is 104.65A; however, the 75°C column ampacity for 3 AWG is 100A, so the OCPD is sized at 100 amperes
  • Adjusted ampacity is 104.65A, so select a 110A OCPD based on the 90°C calculation
  • Adjusted ampacity is 115A because temperature correction does not apply to THHN
  • Adjusted ampacity is 80A, requiring a 80A OCPD

Ready to practice for the Journeyman Electrician License Exam?

Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.

Start free practice →

Frequently Asked Questions

How many Conductor Protection questions are on the Journeyman Electrician License Exam?
The Overcurrent Protection section, which includes Conductor Protection, typically represents a significant portion of the exam. Focus on understanding core concepts rather than memorizing exact question counts, as the exam uses adaptive testing.
What is the best way to study Conductor Protection?
Use active recall and spaced repetition rather than passive reading. Practice with realistic exam questions, review explanations for both correct and incorrect answers, and focus on understanding the reasoning behind each concept.
What topics within Conductor Protection should I focus on most?
Focus on the concepts that appear in our practice questions and any areas where you consistently score below 70%. The adaptive practice mode will automatically target your weak areas for efficient study.