Free Motor Overcurrent Protection (Table 430.52) Practice Questions
Journeyman Electrician License Exam · Motors & Transformers
This module covers Motor Overcurrent Protection (Table 430.52) as part of the Motors & Transformers section, testing your understanding of core concepts and their practical application.
| Exam | Journeyman Electrician License Exam |
| Pass Rate | 55% |
| Duration | 240 minutes |
| Module | Motor Overcurrent Protection (Table 430.52) |
Why Motor Overcurrent Protection (Table 430.52) matters
Motor Overcurrent Protection (Table 430.52) is one of the most tested NEC topics because improper grounding and protection cause electrical fires and fatalities.
Sample Practice Questions (5)
1. A 30-HP, 460V, 3-phase motor has an FLC of 40 amps per Table 430.250. You want to use a dual-element fuse. What is the maximum fuse size, and what is the minimum conductor size (75°C THWN copper)?
- 70A fuse, 8 AWG conductor
- 80A fuse, 6 AWG conductor
- 70A fuse, 6 AWG conductor
- 60A fuse, 8 AWG conductor
2. A 50-HP, 230V, 3-phase motor has an FLC of 130 amps per Table 430.250. What is the maximum inverse time circuit breaker size? (Standard sizes: ...300, 350, 400)
- 300 amps
- 325 amps
- 350 amps
- 400 amps
3. A 20-HP, 230V, 3-phase motor has an FLC of 54 amps per Table 430.250. The motor has difficulty starting with the standard 250% inverse time breaker. Per Exception No. 1 (430.52(C)(1)), what is the maximum breaker size? (Standard sizes: ...150, 175, 200, 225, 250)
- 135 amps
- 150 amps
- 200 amps
- 225 amps
Want more practice like this?
Start practicing free →4. Per NEC 430.52(C)(1) Exception No. 1, if the values from Table 430.52 do not allow the motor to start, the inverse time breaker may be increased up to what maximum percentage of FLC?
- 300%
- 400%
- 350%
- 500%
5. A 5-HP, 208V, 3-phase motor has an FLC of 16.7 amps per Table 430.250. What is the maximum dual-element (time-delay) fuse size? (Standard fuse sizes: 15, 20, 25, 30, 35, 40, 45, 50, 60)
- 25 amps
- 30 amps
- 35 amps
- 40 amps