TL;DR
Master motor circuit design including conductor sizing, overcurrent protection, and control circuit wiring. Motor installations are complex and represent a significant portion of electrician exams.
Free Motor FLC & Conductor Sizing Practice Questions
Journeyman Electrician License Exam · Motors & Transformers
This module covers Motor FLC & Conductor Sizing as part of the Motors & Transformers section, testing your understanding of core concepts and their practical application.
| Exam | Journeyman Electrician License Exam |
| Pass Rate | 55% |
| Duration | 240 minutes |
| Module | Motor FLC & Conductor Sizing |
Why Motor FLC & Conductor Sizing matters
Motor FLC & Conductor Sizing is heavily tested because undersized conductors and services cause overheating, fires, and equipment failure.
Sample Practice Questions (5)
1. A 3-HP, 208V, 3-phase motor has an FLC of 10.6 amps per Table 430.250. If the ambient temperature is 40°C and THWN-2 (90°C) conductors are used but terminated at 75°C equipment, what is the minimum conductor size? (Table 310.16 correction factor for 40°C at 90°C = 0.91)
- 14 AWG
- 12 AWG
- 10 AWG
- 8 AWG
2. A 15-HP, 230V, 3-phase motor has an FLC of 42 amps per Table 430.250. The conductors are THWN copper in a conduit with an ambient temperature of 30°C. What is the minimum conductor size per Table 310.16 (75°C column)?
- 8 AWG (50A)
- 6 AWG (65A)
- 10 AWG (35A)
- 4 AWG (85A)
3. Per NEC Table 430.248, a 3-HP, 230V, single-phase motor has an FLC of 17 amps. The branch-circuit conductors must be sized at 125% of FLC. What minimum THWN copper conductor size is needed per Table 310.16 (75°C column)?
- 14 AWG (20A)
- 12 AWG (25A)
- 10 AWG (35A)
- 8 AWG (50A)
Want more practice like this?
Start practicing free →4. A 10-HP, 460V, 3-phase motor has an FLC of 14 amps per Table 430.250. Using Table 310.16 (75°C copper, THWN), what is the minimum conductor size?
- 14 AWG
- 12 AWG
- 10 AWG
- 8 AWG
5. Per NEC Table 430.250, a 25-HP, 208V, 3-phase motor has a full-load current of 74.8 amps. What is the minimum conductor ampacity?
- 74.8 amps
- 86 amps
- 93.5 amps
- 112.2 amps
Ready to practice for the Journeyman Electrician License Exam?
Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.
Start free practice →