TL;DR
Learn to interpret graphs, charts, and data tables accurately. Data interpretation skills support technical reading and decision-making in the trades.
Free GEC Sizing (Table 250.66) Practice Questions
Journeyman Electrician License Exam · Grounding & Bonding
This module covers GEC Sizing (Table 250.66) as part of the Grounding & Bonding section, testing your understanding of core concepts and their practical application.
| Exam | Journeyman Electrician License Exam |
| Pass Rate | 55% |
| Duration | 240 minutes |
| Module | GEC Sizing (Table 250.66) |
Why GEC Sizing (Table 250.66) matters
GEC Sizing (Table 250.66) is heavily tested because undersized conductors and services cause overheating, fires, and equipment failure.
Sample Practice Questions (5)
1. A 200-ampere service is supplied by two sets of 3/0 AWG copper conductors in parallel. Per NEC Table 250.66, the equivalent single conductor area is used to size the GEC. 3/0 AWG copper = 167,800 CM. Two sets = 335,600 CM, which is closest to 350 kcmil. The minimum copper GEC is:
- 4 AWG
- 2 AWG
- 1/0 AWG
- 6 AWG
2. Per NEC Table 250.66, if the largest ungrounded service-entrance conductor is 1000 kcmil copper, the minimum size copper GEC is:
- 1/0 AWG
- 2/0 AWG
- 3/0 AWG
- 4/0 AWG
3. Per NEC 250.64(E), when a grounding electrode conductor (GEC) is enclosed in a ferromagnetic (steel/iron) raceway, the raceway shall be:
- Grounded at one end only
- Bonded to the GEC at both ends of the raceway
- Painted to prevent corrosion
- No larger than 1 inch trade size
Want more practice like this?
Start practicing free →4. A 1600-ampere service uses four sets of 500 kcmil copper service-entrance conductors per phase. Per the note to NEC Table 250.66, when service-entrance conductors exceed 1100 kcmil copper, the GEC shall be not less than _____ of the equivalent area of the largest ungrounded conductor.
- 10%
- 12.5%
- 15%
- 20%
5. Per NEC Table 250.66, if the largest ungrounded service-entrance conductor is 4/0 AWG aluminum, the minimum size copper GEC is:
- 6 AWG
- 4 AWG
- 2 AWG
- 8 AWG
Ready to practice for the Journeyman Electrician License Exam?
Adaptive practice powered by Item Response Theory targets your weak areas. Start with 3 free sessions.
Start free practice →